Suntree SUP2-PV · 2P · 500 V DC · 20 / 40 kA
Exact reference · SUP2-PV-2P-500V
Two-module photovoltaic surge protector, connected in parallel with the DC circuit. Diverts transient surges to protective earth; separate overcurrent protection is required. Uc and Up depend on the hardware revision, not the nominal 500 V designation alone.
- Nominal discharge current In (8/20 µs)
- 20 kA
- Maximum discharge current Imax (8/20 µs)
- 40 kA
- Nominal DC designation
- 500 V DC
- Uc / Up
- Revision-dependent · not confirmed for supply
- Conductor arrangement
- DC + / DC − + PE
The retained SUP2-PV family table and photographed hardware show different Uc / Up revisions. No single Uc or Up is assigned to this supply record. Select against cold-weather PV open-circuit voltage and equipment impulse withstand using the exact delivered nameplate and applicable manufacturer record. Do not treat the nominal DC designation as the permissible PV voltage.
Pricing confirmed by quote
Quote confirms reference and commercial terms; installation selection remains the installer’s responsibility.
Availability confirmed in your written quote
01 · Product role
What this product does in the system.
Two-module photovoltaic surge protector, connected in parallel with the DC circuit. Diverts transient surges to protective earth; separate overcurrent protection is required. Uc and Up depend on the hardware revision, not the nominal 500 V designation alone.
Relevant applications
- PV combiner and inverter DC circuits
Why ReneWave may shortlist it
- Two-module photovoltaic surge protector, connected in parallel with the DC circuit. Diverts transient surges to protective earth; separate overcurrent protection is required. Uc and Up depend on the hardware revision, not the nominal 500 V designation alone.
What changes in practice
- Connect the complete SPD assembly in parallel between DC +, DC − and the earth bar according to its terminal drawing. Three modules do not mean three PV strings or three switched poles. PE is always connected, never switched.
- In is the nominal surge-discharge current and Imax the maximum surge-discharge current, both for an 8/20 µs pulse. They are not a 40 kA breaker rating. Coordinate backup protection, earth bonding and equipment impulse withstand; a rated backup fuse size is not established here.
- Surge diversion only. No overload, short-circuit or residual-current protection; no protection guarantee against a direct lightning strike. Keep the circuit’s isolation and overcurrent devices separate.
System position
Parallel surge diversion, not series interruption.
Surge diversion only. No overload, short-circuit or residual-current protection; no protection guarantee against a direct lightning strike. Keep the circuit’s isolation and overcurrent devices separate.
The circuit supplies the load; the SPD is connected in parallel, not in series with the load.
Read the technical explanation
Two-module photovoltaic surge protector, connected in parallel with the DC circuit. Diverts transient surges to protective earth; separate overcurrent protection is required. Uc and Up depend on the hardware revision, not the nominal 500 V designation alone.
Connect the complete SPD assembly in parallel between DC +, DC − and the earth bar according to its terminal drawing. Three modules do not mean three PV strings or three switched poles. PE is always connected, never switched.
Surge diversion only. No overload, short-circuit or residual-current protection; no protection guarantee against a direct lightning strike. Keep the circuit’s isolation and overcurrent devices separate.
The retained SUP2-PV family table and photographed hardware show different Uc / Up revisions. No single Uc or Up is assigned to this supply record. Select against cold-weather PV open-circuit voltage and equipment impulse withstand using the exact delivered nameplate and applicable manufacturer record. Do not treat the nominal DC designation as the permissible PV voltage.
02 · Specifications
Ratings, dimensions and practical consequence.
Device identity and surge ratings
- Manufacturer reference
SUP2-PV
- Selected configuration
2P · 500 V DC · In 20 kA / Imax 40 kA
- Circuit application
DC · PV
- Catalog configuration ID
SUP2-PV-2P-500V
- Nominal discharge current In (8/20 µs)
20 kA
- Maximum discharge current Imax (8/20 µs)
40 kA
- Nominal DC designation
500 V DC
- Uc / Up
Revision-dependent · not confirmed for supply
- Conductor arrangement
DC + / DC − + PE
03 · Selection points
Four practical selection points.
Match the circuit, surge ratings, earth connection and backup protection.
- 01

Circuit and conductor arrangement
Connect the complete SPD assembly in parallel between DC +, DC − and the earth bar according to its terminal drawing. Three modules do not mean three PV strings or three switched poles. PE is always connected, never switched.
- 02

Voltage and surge ratings
The retained SUP2-PV family table and photographed hardware show different Uc / Up revisions. No single Uc or Up is assigned to this supply record. Select against cold-weather PV open-circuit voltage and equipment impulse withstand using the exact delivered nameplate and applicable manufacturer record. Do not treat the nominal DC designation as the permissible PV voltage.
- 03

Separate backup protection
In is the nominal surge-discharge current and Imax the maximum surge-discharge current, both for an 8/20 µs pulse. They are not a 40 kA breaker rating. Coordinate backup protection, earth bonding and equipment impulse withstand; a rated backup fuse size is not established here.
- 04

Mounting and earth connection
35 mm DIN rail mounting inside a suitable enclosure. Keep the parallel conductors and PE connection short. Follow the supplied revision’s terminal drawing; isolate before replacing a module. A red status window calls for inspection and replacement, not automatic resetting.
04 · Documentation
Keep the exact reference traceable.
Published documents for this exact reference support selection and handover.
05 · Complete the system
Accessories and adjacent equipment, in one request.
Separate equipment is selected for the installation; no automatic companions are added to your request.
No automatic companion selection. Separate protection and accessories are chosen for the installation.