Four independent PV operating points
Four MPPTs can track four deliberately grouped array zones.
Huawei publishes eight inputs, 27 A maximum per MPPT, 20 A per input and 40 A maximum short-circuit current per MPPT.

Exact reference · SUN2000-30KTL-M3
A 30 kW commercial grid-following inverter with four independent MPPTs and eight PV inputs. It has no battery interface, backup output, transfer switch or off-grid mode.
Defines the inverter output class; it does not approve the site service or connected demand.
Two inputs per tracker still require compatible string voltage and current.
Each string must remain in range across temperature, and full output requires the narrower voltage window.
High-current modules and parallel strings require explicit current validation.
The inverter converts available PV power only while a valid AC reference is present.
Do not select the 30 kW reference from nominal power alone. Confirm every string, MPPT allocation, full-load voltage, AC service, protection, grid code and monitoring architecture.
Pricing confirmed by quote
The written quote confirms the exact reference, required accessories, compatibility, delivery and commercial terms.
Availability confirmed in your written quote
01 · Product role
The SUN2000-30KTL-M3 converts DC power from up to eight deliberately allocated PV string inputs into grid-synchronised three-phase AC. Its four MPPTs can track four suitable operating points, while protected distribution and the utility remain directly connected on the AC side. It does not accept batteries, transfer utility power or energise backup loads during an outage.
Relevant applications
Why ReneWave may shortlist it
Built-in capabilities
Four MPPTs can track four deliberately grouped array zones.
Huawei publishes eight inputs, 27 A maximum per MPPT, 20 A per input and 40 A maximum short-circuit current per MPPT.

The inverter converts available PV power into synchronised AC for protected commercial distribution.
Rated output is 30,000 W with 33,000 VA maximum apparent power.

Integrated string monitoring supports commissioning and fault investigation.
RS485, integrated WLAN and optional communications dongles connect the reviewed plant-monitoring architecture.

AFCI and Type II AC/DC surge protection are part of the published inverter functions.
Project-specific isolation, protection coordination, conductors and earthing remain external design work.
Inside the energy system
Solar conversion follows the utility AC reference. No battery or backup path is shown.
Eight designed inputs pass through four MPPTs and the M3 to serve protected three-phase site loads while utility remains the required AC reference.
Four independent trackers for a deliberately structured commercial array.
The SUN2000-30KTL-M3 converts photovoltaic DC into grid-synchronised three-phase AC. Four trackers and eight inputs help separate suitable string groups, but every input and combined tracker still requires calculation.
A commercial string inverter, not a hybrid inverter
This reference has no battery interface, transfer switch, backup output or off-grid mode. Protected AC distribution, metering, plant control, external protection and communications accessories remain part of the project design.
Full-load voltage matters
The broad 200–1,000 V MPPT window keeps the inverter tracking, while the narrower 500–800 V range applies when the project expects full output at 380/400 V.
02 · Specifications
1,100 V
200 V · 600 V
200–1,000 V
500–800 V
4 MPPTs · 8 inputs total
27 A per MPPT · 20 A per input · 40 A maximum Isc per MPPT
30,000 W
33,000 VA
43.3 A · 47.9 A
230/400 V · 3W/N+PE · 50/60 Hz
98.7% · 98.4%
String monitoring · AFCI · Type II AC/DC surge protection
RS485 · integrated WLAN · optional communications dongles
IP66 · natural convection
640 × 530 × 270 mm
43 kg
03 · Confirm before quotation
ReneWave confirms the electrical context, connected equipment, installation conditions and configuration path before the exact reference enters a written quote.

Confirm cold Voc, operating voltage, current, module count and allocation for all eight inputs and four trackers.

Confirm the service voltage, phase arrangement, 50 Hz grid code, anti-islanding, full-load range and AC current.

Confirm isolation, conductors, surge coordination, earthing, mounting clearances and the exact supplied connectors.

Confirm RS485 topology, metering, SmartLogger or dongle needs, FusionSolar ownership and commissioned settings.
04 · Documents & warranty
Documents shown here support selection and handover. The accepted order and exact manufacturer warranty document control.
5 years · current non-European C&I policy
05 · Complete the system
Select relevant companions now. ReneWave still verifies quantities and compatibility before they appear in the written quote.
Recommended companions

Huawei FusionSolar · SMARTLOGGER3000A
Huawei SmartLogger3000A PV Plant Communications ControllerAdds plant-level communications, commissioning and supported control coordination. Use only after the exact SmartLogger suffix, plant RS485 topology, inverter firmware and commissioned control architecture are confirmed.

CHINT · DTSU666-H-100A
CHINT DTSU666-H 100 A Three-Phase Smart Power SensorAdds three-phase current, voltage, power and energy measurement for a compatible Huawei control architecture. Confirm that the 100 A CT package matches the point of measurement, then verify CT orientation, phase sequence, RS485 topology and firmware.
RENEWAVEEnergy systems, held to standard.