Two PV operating points
Two MPPTs track two separately calculated PV strings.
Each tracker is limited to 13 A operating current and 17 A short-circuit current.

Exact reference · SUN-5K-SG05LP1-EU
A single-phase hybrid inverter integrating two PV trackers, solar conversion, a bidirectional 48 V battery inverter/charger and a dedicated selected-load output. The battery, BMS, protection, meter, generator and installation remain separate.
Defines the output class; selected-load demand and surge behavior still require calculation.
One calculated string per tracker must remain inside voltage and current limits.
Cold string voltage and normal operation must both remain within the published boundaries.
Battery chemistry, BMS, conductors and protection determine whether the system can use the limit safely.
This is a short published surge condition, not permission to place the complete site on the protected output.
Do not select this inverter from 5 kW or 48 V alone. Confirm PV current, battery and BMS behavior, load demand, surge requirements, AC architecture and generator-port configuration.
Pricing confirmed by quote
The written quote confirms the exact reference, required accessories, compatibility, delivery and commercial terms.
Availability confirmed in your written quote
01 · Product role
The SUN-5K-SG05LP1-EU receives DC power from two designed PV strings, converts it into single-phase AC and can charge or discharge a separately selected 48 V battery. Its dedicated load output can support selected circuits during an outage. Utility, generator, battery and load paths still require external protection, compatible equipment and commissioned settings.
Relevant applications
Why ReneWave may shortlist it
Built-in capabilities
Two MPPTs track two separately calculated PV strings.
Each tracker is limited to 13 A operating current and 17 A short-circuit current.

Available PV power is converted into controlled 220/230 V single-phase AC.
Rated output is 5,000 W with 5,500 VA maximum apparent power.

The inverter can charge and discharge a separately selected 40–60 V battery system.
The published maximum charge and discharge current is 120 A.

Dedicated grid, protected-load and configurable GEN interfaces coordinate valid operating states.
The GEN port is assigned one commissioned function at a time.
Inside the energy system
Solar conversion inside the inverter. Storage, external protection and configured load circuits remain separate.
PV passes through both MPPTs and the inverter to serve the selected protected-load circuit.
The GEN port is configured for one role at a time. This diagram shows generator input only in Generator support mode.
Solar conversion, 48 V storage and selected-load backup in one coordinated inverter.
The Deye SUN-5K-SG05LP1-EU combines two photovoltaic trackers, single-phase conversion, a bidirectional low-voltage battery inverter/charger and a dedicated protected-load output. It can coordinate utility or a separately configured generator input, but the complete system still requires the correct battery, BMS, metering, external protection and commissioned settings.
Functional boundary
The GEN port is configurable. It cannot be generator input, smart-load output and AC-coupling input at the same time. Backup capability applies to the deliberately selected and protected load circuit, not automatically to every site load.
02 · Specifications
6,500 W
2 MPPTs · 1 string each
150–425 V MPPT · 500 V maximum · 125 V startup
13 A operating · 17 A Isc per MPPT
5,000 W · 5,500 VA
220/230 V · L+N+PE · 50/60 Hz
97.6% maximum · 96.5% European weighted
2× rated power for 10 seconds
40–60 V · lead-acid or compatible lithium
120 A maximum
Configurable GEN port · one role at a time
Up to 16 documented units under validated conditions
330 × 580 × 232 mm
24.9 kg
IP65 · intelligent air cooling
<30 dB published level
03 · Confirm before quotation
ReneWave confirms the electrical context, connected equipment, installation conditions and configuration path before the exact reference enters a written quote.

Confirm cold Voc, operating voltage, 13 A operating current, 17 A Isc, module count and one-string allocation per tracker.

Confirm 40–60 V battery behavior, chemistry, BMS, 120 A current path, usable capacity, load demand and surge.

Confirm utility service, dedicated protected circuits, isolation, conductors, protection, earthing and cooling clearances.

Confirm the single GEN-port role, CT/meter direction, firmware, communications, parallel settings and operating schedule.
04 · Documents & warranty
Documents shown here support selection and handover. The accepted order and exact manufacturer warranty document control.
5 years standard · optional extension only when ordered