    ABB S803N-C125 · thermal-magnetic 3P breaker

    Exact reference · S803N-C125

    Protects the selected circuit against overload and short circuit. The current rating and trip curve must suit the load, conductors and installation.

    Protection function
    Thermal-magnetic overload and short-circuit protection
    Poles
    3
    Rated current
    125 A · C curve

    No integrated residual-current protection. Use separately selected earth-leakage protection where required.

    Pricing confirmed by quote

    Quote confirms reference and commercial terms; installation selection remains the installer’s responsibility.

    Availability confirmed in your written quote

    1

    01 · Product role

    What this product does in the system.

    Protects the selected circuit against overload and short circuit. The current rating and trip curve must suit the load, conductors and installation.

    Relevant applications

    • Selected three-phase commercial or equipment circuits.

    Why ReneWave may shortlist it

    • Protects the selected circuit against overload and short circuit. The current rating and trip curve must suit the load, conductors and installation.

    System position

    Three-phase AC circuit: conceptual single-line view.

    No integrated residual-current protection. Use separately selected earth-leakage protection where required.

    The selected three-phase circuit is supplied through the closed device. Separate equipment is illustrative, not included or automatically recommended.

    Protects the selected circuit against overload and short circuit. The current rating and trip curve must suit the load, conductors and installation. The selected three-phase circuit is supplied through the closed device. Separate equipment is illustrative, not included or automatically recommended.Three-phase AC supplyL1 / L2 / L3S803N-C125125 A · C curveCommercial distributionSeparate branch protectionSelected site circuitsLoad / conductors selectedProtects the selected circuit against overload and short circuit. The current rating and trip curve must suit the load, conductors and installation. The selected three-phase circuit is supplied through the closed device. Separate equipment is illustrative, not included or automatically recommended.Three-phase AC supplyL1 / L2 / L3S803N-C125125 A · C curveCommercial distributionSeparate branch protectionSelected site circuitsLoad / conductors selectedProtects the selected circuit against overload and short circuit. The current rating and trip curve must suit the load, conductors and installation. The selected three-phase circuit is supplied through the closed device. Separate equipment is illustrative, not included or automatically recommended.Three-phase AC supplyL1 / L2 / L3S803N-C125125 A · C curveCommercial distributionSeparate branch protectionSelected site circuitsLoad / conductors selected
    Read the technical explanation

    No integrated residual-current protection. Use separately selected earth-leakage protection where required.

    02 · Specifications

    Ratings, dimensions and practical consequence.

    Device identity

    ABB reference

    S803N-C125

    ABB article code

    2CCS893001R0844

    Protection function

    Thermal-magnetic overload and short-circuit protection

    Poles

    3

    Rated current

    125 A · C curve

    Rated operational voltage

    690 V AC · IEC/EN 60947-2

    Breaking capacity by voltage

    Icu · IEC/EN 60947-2

    36 kA · 415 V AC; 20 kA · 440 V AC; 4.5 kA · 690 V AC

    Ics · IEC/EN 60947-2

    30 kA · 415 V AC; 3 kA · 690 V AC

    03 · Selection points

    Four practical selection points.

    Match the device to the circuit, expected load and fault conditions. Request a quote for the exact reference you have selected.

    1. 01

      Pole configuration

      Three protected poles for L1, L2 and L3. No neutral pole: do not substitute it for a 3P+N or 4P device.

    2. 02

      Current and trip function

      Protects the selected circuit against overload and short circuit. The current rating and trip curve must suit the load, conductors and installation.

    3. 03

      Voltage and fault capacity

      Compare the prospective fault current with the capacity at the actual supply voltage and standard. Icn, Icu and Ics are different ratings, not interchangeable labels.

    4. 04

      Mounting and connections

      DIN-rail mounting; use the ABB terminal limits and tightening torque in the installation document.

    04 · Documentation

    Keep the exact reference traceable.

    Published documents for this exact reference support selection and handover.

    05 · Complete the system

    Accessories and adjacent equipment, in one request.

    Separate equipment is selected for the installation; no automatic companions are added to your request.

    No automatic companion selection. Separate protection and accessories are chosen for the installation.

    Compare products
    ReneWave markRENEWAVE

    Energy systems, held to standard.