Stores DC energy
Provides a rate-defined 12 V GEL storage increment.
100 Ah at the ten-hour test; no independent AC output.

Exact reference · OT100-12(GEL)/CD
Rate-defined 12 V GEL storage for a deliberately designed battery bank and inverter/charger.
An early-cycle average, not a guaranteed minimum.
Use the relevant discharge test for autonomy calculations.
Float charging is 13.6–13.8 V at 25°C; temperature compensation must be configured.
Support, termination and protective measures require review.
Do not select this battery from 100 Ah or “12 V” alone. Confirm autonomy, discharge rate, bank voltage, matched battery count, charge settings, temperature compensation, conductors, protection, ventilation and handling.
Pricing confirmed by quote
The written quote confirms the exact reference, required accessories, compatibility, delivery and commercial terms.
Availability confirmed in your written quote
01 · Product role
A sealed GEL lead-acid battery for a deliberately designed DC bank and compatible inverter/charger. It contains no inverter, MPPT, AC charger, BMS communications, transfer switch or independent AC output. Capacity depends on discharge rate, cutoff voltage, temperature, storage history, age and charging conditions.
Relevant applications
Why ReneWave may shortlist it
Built-in capabilities

Provides a rate-defined 12 V GEL storage increment.
100 Ah at the ten-hour test; no independent AC output.

Supports controlled cyclic lead-acid service.
Sealed construction does not remove ventilation requirements.

Requires a compatible external charger.
Initial charging below 30 A; cycle and float voltage settings are distinct.

Publishes one-, three- and ten-hour capacity records.
Do not apply the C10 capacity unchanged at a higher discharge rate.
System position
PV conversion, inverter/charger and AC distribution are separate equipment. No direct PV-to-battery, battery-to-AC-load, standalone backup or grid-export path is represented.
Solar supplies protected loads through the inverter while the battery bank is idle.
A sealed GEL lead-acid battery for a deliberately designed DC bank and compatible inverter/charger. It contains no inverter, MPPT, AC charger, BMS communications, transfer switch or independent AC output. Capacity depends on discharge rate, cutoff voltage, temperature, storage history, age and charging conditions.
The manufacturer sheet reports averages from the first three charge/discharge cycles, not guaranteed minimum values. The historical grey-container /CD reference is not interchangeable with current DS, CN or digital-screen models. Do not select this battery from 100 Ah or “12 V” alone. Confirm autonomy, discharge rate, bank voltage, matched battery count, charge settings, temperature compensation, conductors, protection, ventilation and handling.
02 · Specifications
12 V
100 Ah at 10 A and 25°C
Approximately 1.2 kWh · not usable energy
79 Ah at 25 A
61 Ah at 55 A
Less than 30 A
14.5–14.9 V at 25°C
13.6–13.8 V at 25°C
5 mΩ fully charged at 25°C
T3 arrangement · M8 connection
333 × 173 × 216 mm (±2 mm)
222 mm (±2 mm)
Approximately 30.5 kg
03 · Confirm before quotation
ReneWave confirms the electrical context, connected equipment, installation conditions and configuration path before the exact reference enters a written quote.

Confirm voltage, matched battery quantity and series/parallel design.

Calculate autonomy for load, cutoff voltage, temperature and age.

Design conductors, fusing, isolation, ventilation and structural support.

Verify GEL settings, temperature compensation, exact nameplate and commissioning.
04 · Documentation
Published documents for this exact reference support selection and handover.
05 · Complete the system
Select relevant companions now. ReneWave still verifies quantities and compatibility before they appear in the written quote.
No additional equipment is published for this reference. Required accessories are confirmed during quotation.
RENEWAVEEnergy systems, held to standard.