    ABB A1N 125 TMF 80-800 4p F F · 80 A · 4P molded-case breaker

    Exact reference · A1N 125 TMF 80-800 4p F F

    A four-pole molded-case breaker with fixed thermal overload protection at 80 A and fixed magnetic short-circuit threshold at 800 A. The 125 A frame is not the selected trip rating. No residual-current function is built in.

    Protection function
    Thermal-magnetic overload and short-circuit protection
    Poles
    4
    Neutral protection
    4 protected poles · neutral at 100%

    No integrated residual-current protection. Use separately selected earth-leakage protection where required. L1, L2, L3 and N are jointly switched. The FORMULA catalogue specifies neutral protection at 100% of the phase rating: 80 A thermal and 800 A magnetic for this TMF selection. Protective earth is never switched.

    Pricing confirmed by quote

    Quote confirms reference and commercial terms; installation selection remains the installer’s responsibility.

    Availability confirmed in your written quote

    1

    01 · Product role

    What this product does in the system.

    A four-pole molded-case breaker with fixed thermal overload protection at 80 A and fixed magnetic short-circuit threshold at 800 A. The 125 A frame is not the selected trip rating. No residual-current function is built in.

    Relevant applications

    • Selected commercial distribution with L1, L2, L3 and N.

    Why ReneWave may shortlist it

    • A four-pole molded-case breaker with fixed thermal overload protection at 80 A and fixed magnetic short-circuit threshold at 800 A. The 125 A frame is not the selected trip rating. No residual-current function is built in.

    System position

    Four-pole commercial distribution: L1, L2, L3 and N.

    No integrated residual-current protection. Use separately selected earth-leakage protection where required. L1, L2, L3 and N are jointly switched. The FORMULA catalogue specifies neutral protection at 100% of the phase rating: 80 A thermal and 800 A magnetic for this TMF selection. Protective earth is never switched.

    The closed four-pole device supplies L1, L2, L3 and N to commercial distribution. Protective earth bypasses the device and is never switched. Branch devices are separate, not included.

    A four-pole molded-case breaker with fixed thermal overload protection at 80 A and fixed magnetic short-circuit threshold at 800 A. The 125 A frame is not the selected trip rating. No residual-current function is built in. The closed four-pole device supplies L1, L2, L3 and N to commercial distribution. Protective earth bypasses the device and is never switched. Branch devices are separate, not included.Three-phase AC supplyL1 / L2 / L3 / NA1N 125 TMF 80-800 · 4P 1SDA066765R180 ACommercial distributionSeparate branch protectionSelected site circuitsLoad / conductors selectedA four-pole molded-case breaker with fixed thermal overload protection at 80 A and fixed magnetic short-circuit threshold at 800 A. The 125 A frame is not the selected trip rating. No residual-current function is built in. The closed four-pole device supplies L1, L2, L3 and N to commercial distribution. Protective earth bypasses the device and is never switched. Branch devices are separate, not included.Three-phase AC supplyL1 / L2 / L3 / NA1N 125 TMF 80-800 · 4P 1SDA066765R180 ACommercial distributionSeparate branch protectionSelected site circuitsLoad / conductors selectedA four-pole molded-case breaker with fixed thermal overload protection at 80 A and fixed magnetic short-circuit threshold at 800 A. The 125 A frame is not the selected trip rating. No residual-current function is built in. The closed four-pole device supplies L1, L2, L3 and N to commercial distribution. Protective earth bypasses the device and is never switched. Branch devices are separate, not included.Three-phase AC supplyL1 / L2 / L3 / NA1N 125 TMF 80-800 · 4P 1SDA066765R180 ACommercial distributionSeparate branch protectionSelected site circuitsLoad / conductors selected

    Electrical power · L1 / L2 / L3 / NPE · Always connected, never switchedInactive / conditional

    Conceptual system position, not an installation drawing. Separate equipment and commissioning must be verified.

    Read the technical explanation

    No integrated residual-current protection. Use separately selected earth-leakage protection where required. L1, L2, L3 and N are jointly switched. The FORMULA catalogue specifies neutral protection at 100% of the phase rating: 80 A thermal and 800 A magnetic for this TMF selection. Protective earth is never switched.

    02 · Specifications

    Ratings, dimensions and practical consequence.

    Device identity

    ABB reference

    A1N 125 TMF 80-800 4p F F

    ABB article code

    1SDA066765R1

    Protection function

    Thermal-magnetic overload and short-circuit protection

    Poles

    4

    Neutral protection

    L1, L2, L3 and N are jointly switched. The FORMULA catalogue specifies neutral protection at 100% of the phase rating: 80 A thermal and 800 A magnetic for this TMF selection. Protective earth is never switched.

    Rated current

    80 A

    Rated operational voltage

    550 V AC · IEC/EN 60947-2

    Trip unit / frame

    80 A trip rating · 125 A frame

    Fixed magnetic threshold

    800 A

    Breaking capacity by voltage

    Icu · IEC/EN 60947-2

    36 kA · 380 / 415 V AC; 25 kA · 440 V AC; 18 kA · 480 V AC; 10 kA · 500 V AC

    Ics · IEC/EN 60947-2

    18 kA · 380 V AC; 7.5 kA · 415 V AC; 6.25 kA · 440 V AC; 4.5 kA · 480 V AC; 2.5 kA · 500 V AC

    03 · Selection points

    Four practical selection points.

    Match the device to the circuit, expected load and fault conditions. Request a quote for the exact reference you have selected.

    1. 01

      Pole configuration

      L1, L2, L3 and N are jointly switched. The FORMULA catalogue specifies neutral protection at 100% of the phase rating: 80 A thermal and 800 A magnetic for this TMF selection. Protective earth is never switched.

    2. 02

      Current and trip function

      A four-pole molded-case breaker with fixed thermal overload protection at 80 A and fixed magnetic short-circuit threshold at 800 A. The 125 A frame is not the selected trip rating. No residual-current function is built in.

    3. 03

      Voltage and fault capacity

      Compare the prospective fault current with the capacity at the actual supply voltage and standard. Icn, Icu and Ics are different ratings, not interchangeable labels. The 240 V breaking-capacity row is withheld because ABB source revisions disagree. Do not substitute it for the verified 380 / 415 V ratings.

    4. 04

      Mounting and connections

      Fixed molded-case installation with front terminals. Use the ABB A1 mounting and connection instructions; this is not a modular DIN-rail breaker. TMF thermal and magnetic thresholds are fixed, not user-adjustable.

    04 · Documentation

    Keep the exact reference traceable.

    Published documents for this exact reference support selection and handover.

    Partial document record

    Available verified documents at review date

    International / Morocco · English / Multilingual · reviewed 2026-09-30

    Official technical records and applicable family instructions are retained locally. Package contents, complete library inventory and commercial evidence are not approved.

    ABB A1N 125 TMF 80-800 4p F F · technical datadatasheet · International · EnglishABB product-page export · 2026-09-30 · exact reference
    View PDF Download PDF
    ABB FORMULA · technical cataloguedatasheet · International · English1SDC210032D0204 · product family
    View PDF Download PDF
    ABB FORMULA A1 · installation instructionsinstallation · International · Multilingual1SDH000717R0001 · product family
    View PDF Download PDF
    ABB FORMULA · declaration of conformitycertificate · International · English9AKK106713A5519 · product family
    View PDF Download PDF

    05 · Complete the system

    Accessories and adjacent equipment, in one request.

    Separate equipment is selected for the installation; no automatic companions are added to your request.

    No automatic companion selection. Separate protection and accessories are chosen for the installation.

    Compare products
    1
    ReneWave markRENEWAVE

    Energy systems, held to standard.

    ReneWave updates · You choose the topics

    Solar, maintenance, practical guides and selected offers.

    Pick one stream or several. Offers stay separate from editorial updates, and every email includes a one-click unsubscribe.

    Choose your updates

    Let’s redefine energy
    together.

    Engineer-led Solar delivery and audit-led maintenance for Moroccan homes, hospitality, agriculture, industry and professional buildings.

    Start a conversation

    Services

    • All Services
    • ReneWave Solar
    • ReneWcare Max
    • Start a Solar Project
    • Start a ReneWcare Assessment

    Store & Tools

    • Equipment Store
    • Solar Calculator
    • Maintenance Priorities
    • Record a Breakdown
    • All Tools

    Knowledge

    • Knowledge Hub
    • Journal
    • Newsroom
    • FAQ
    • Technical Library
    • Applications
    • Solar Technology
    • Maintenance Technology
    • Brand Partners
    • Energy Audit Playbook

    Company

    • Our Company
    • Our Mission
    • Meet Us
    • Engineering Method
    • Contact
    • Support, Warranty & Returns
    • Terms & Policies

    © 2026 ReneWave Morocco / All rights reserved

    Terms of SaleWarrantiesReturns & RefundsDelivery & InstallationPrivacy & CookiesClaims & After-Sales
    Engineering-led / Made in Morocco
    Edit with